3VA2025-6HM32-0AA0 | Siemens
Circuit breaker, 3 pole, H Curve, 25 A, DIN rail, 3VA2025-6HM32-0AA0
As a private customer, you can buy this item as soon as we have it back in stock.
Circuit breaker 3VA2 IEC frame 100 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU330, LIG, In=25A overload protection Ir=10A...25A short-circuit protection Ii=1.5...12 x In ground-fault protection Ig=0.6... 1 x In, tg=0.1/0.3s nut keeper kit 3VA2 molded-case circuit breaker with 8-series ETU for system protection.As an important element of SENTRON protective components for industrial and infrastructure applications, the 3VA molded-case circuit breakers from Siemens provide effective plant, starter and Motor protection thanks to reliable shutdown in the event of an overload or short circuit. The 3VA molded-case circuit breakers set new standards in flexibility and the variety of modular accessories available. Standardized accessories for several sizes across all series of the 3VA1 and 3VA2 molded-case circuit breakers.
Features
- Compact design
- Available as version for plant protection and generator protection
- Can be installed fixed, in plug-in design or as withdrawable version
- The series has a solid-state overcurrent trip unit
- Integrated display for measured values
- Integrated measuring function and optional communication connection via Modbus TCP, Modbus RTU, PROFINET and PROFIBUS
- Modular and easy-to-fit internal accessories with wide range of functions
Filter | Property | Value |
---|---|---|
Degree of protection (IP) | IP40 | |
Assembly | DIN rail | |
Tripping characteristics | H | |
Product type | circuit breaker | |
Rated voltage (AC) | 690 V | |
Pin number | 3 pole | |
Rated current | 25 A |
Property | Value |
---|---|
Country of origin | CZ |
Customs tariff number | 85362010 |
Property | Value |
---|---|
Date of RoHS guidelines | 3/31/15 |
Substance description | Lead, lead monoxide (lead oxide), Silicic acid, lead salt |
SVHC free | No |
RoHS conform | Yes |
Sustainable | Yes |